Cold storage warehouse operator Americold has deployed single-stage compressors in its new 542TR (1.9MW) transcritical CO2 (R744) warehouse in New Brunswick, Canada, according to Phillip Walker, General Manager at TechnoRef4, the engineering firm that designed the system.
Americold opted for a simple design given the mild Canadian climate, Walker noted in a presentation at ATMOsphere America Summit 2026, adding that this marks the logistic provider’s first foray into transcritical CO2 refrigeration. Giacomo Pisano, CO2 Compressors Business Development Manager at Dorin, joined Walker at the conference to outline the operation of single-stage compressors. The event, organized by ATMOsphere, publisher of NaturalRefrigerants.com, took place June 2‒3 in Tarrytown, New York.
The design uses semi-hermetic CO2 compressors to serve both low- and medium-temperature (LT/MT) loads, enabling flexible freezer storage between −19 and 25°F (−28 and −4°C). The grand opening of the new warehouse took place on June 18, according to Americold.
“In our dual temperature design with a split suction header, we removed the booster and all those controls, providing 18.2% CAPEX cost savings for the customer,” Walker said, adding that the simplified single-stage layout also eases system commissioning and maintenance.
The setup: Located at Port Saint John, the 140,000ft2 (13,000m2) warehouse includes a 35,000ft2 (3,250m2) loading dock maintained at 34°F (1°C) and handles a throughput of roughly 3.5 million pounds (1.6 million kilograms) of goods per hour, according to Walker.
- Two nominal 557HP packs, manufactured by Canadian-based Ceptek, provide both MT and LT refrigeration, each delivering 271TR (950kW) of capacity. Each pack includes nine six-cylinder compressors.
- The design includes hot-gas defrost for LT and MT operation, a heat-recovery module with a glycol-pumping skid and adiabatic gas coolers for operation in ambient temperatures above 95°F (35°C).
- The MT loading dock operates with a COP of 6.39, while the LT freezer operates with a COP of 3.27 during daytime active loading. However, when accounting for 5.502MMBtu/h (458TR/1.6MW) of reclaim heat capacity, the site achieves a combined useful COP of 3.41.
Up to the task: In cold-climate applications, single-stage CO2 compressors can operate at evaporating temperatures as low as −20°F (−29°C) while withstanding transcritical pressures of up to 1,250psi (80bar), according to Pisano.
- In addition, the oil sump temperature remains “pretty low” at around 162°F (72°C), resulting in a residual viscosity of 16cSt (centistrokes), which Pisano said indicates adequate lubrication despite high-pressure operation.
- “The message is that single-stage compressors are capable of handling LT conditions, backed by a large safety margin,” Pisano added.
End user wanted: Although the CO2 system generates 5.502MMBtu/h of heat recovery capacity, the warehouse only uses 0.7MMBtu/h (58.3TR/205kW), leaving 4.8MMBtu/h (398.1TR/1.4MW) available for outside use.
- “To maximize full heat reclaim, we are looking to deliver that heat to neighboring sectors either for district heating or process applications,” Walker said.
Quotable: “In this kind of application, you don’t need a booster, and you can do a single-stage suction group with way less complexity,” Pisano said, adding that Dorin’s external discharge plenum keeps the compressor outlet temperature below 300°F (149°C).
“In our dual temperature design with a split suction header, we removed the booster and all those controls, providing 18.2% CAPEX cost savings for the customer.”
Phillip Walker,
General Manager at TechnoRef4