Perfect for supermarkets, food plants, and other non-retail usages with both MT/LT applications. The OCU-CR1000VF8A has optimum operation and quietness by cutting-edge inverter technology

01
Panasonic -10HP Outdoor Condensing Unit (MT & LT) – iCORE OCU-CR
Condensing units with natural refrigerant – The new environmentally friendly CO₂ condensing units for commercial refrigeration.
With Panasonic condensing units you will get energy savings, low noise, reduced weight, low refrigerant charge, low installation costs and low maintenance costs.
Nominal output
15.10kW (MT) / 8.00kW (LT)- Power supply: 3P 400V
Ambient temperature
-15°C – +43°CEvaporating temperature
-45°C to -5°CDesign pressure
HP 8MPa / LP 8MPaCompressor
Two-stage rotary compressorDimensions
H1,941 x W890 x D890
02
Benefits of Panasonic 10HP Outdoor Condensing Unit (MT & LT) – iCORE OCU-CR
- 30% more energy efficient than conventional R404A system
- Compact and light weight design for small format installation
- Easier and flexible installation
02 技術資料
仕様
14項目のデータ · Panasonicの公表値
- 冷媒
- CO₂
- カテゴリー
- Components
01性能
1項目
- Capacity
- Voltage: 3P 400 VEvaporating temperature: -45 °C to -5 °CWith ambient temperature = +32 °C and evaporating temperature = -10 °C: 15.10 kWWith ambient temperature = +32 °C and evaporating temperature = -35 °C: 8.00 kW
02冷媒
2項目
- Refrigerant charge
- Max. gas load (recommended) = 17.0 kg (inner receiver included)
- Refrigerant
- CO₂
03構成部品とオプション
6項目
- Type/number of compressors
- Type: Two-stage rotary compressorManufacturer: PANASONICNb per unit: 1Rotational speed (RPS): 30s-1 to 60s-1
- Oil separator
- Oil separator included (with 3,000 ml of oil)
- Subcooling
- Subcooler included
- Heat reclaim
- Yes
- VFD for compressors
- Variable speed compressor, with inverter technology
- Ejectors/parallel compression
- N/A
04制御と電気仕様
1項目
- Controls
- RS485 modbus connectivityCompatibility confirmed with CAREL, DANFOSS, DIXELL, ELI-WELL, RDM and WURM
05構造と寸法
2項目
- Dimensions
- H1,941 x W890 x D890 mm
- Type of piping
- Suction line: 19.05 mm (outer diameter welding)Liquid line: 15.88 mm (outer diameter welding)
06認証と対応市場
2項目
- Certification
- All major certifications, like CE, are confirmedAny specific request, please contact your local Panasonic office
- Region
- Asia, Australia & NZ, Europe
10HP Outdoor Condensing Unit (MT & LT) – iCORE OCU-CRについてPanasonicに問い合わせる。