Ir al contenido
Beta

Este es el nuevo NaturalRefrigerants.com. ¿Ha detectado un problema técnico o de contenido? Escríbanos a info@naturalrefrigerants.com.

Westermeyer

RDP-01T Differential Pressure Monitor

The RDP-01T Differential Pressure Monitor is part of the Refri-Shield™️ line of system monitoring products.

Esta página de producto aún no está disponible en español: se muestra el original en inglés.

RDP-01T Differential Pressure Monitor

Fig. 01 — RDP-01T Differential Pressure Monitor

01 Resumen

It is designed to indicate when the filter element of a coalescing oil separator needs to be serviced and replaced by measuring the pressure differential across the inlet and outlet. This model features transducers designed for use with CO₂ systems at transcritical pressures.

01

Westermeyer RDP-01T Differential Pressure Monitor When the filter element of a coalescing oil separator is contaminated, performance and efficiency are negatively affected. A differential pressure monitor is used to monitor, both visually and electronically, when the filter is contaminated and needs to be replaced. 

The Refri-Shield™️ RDP-01T Differential Pressure Monitor is factory-calibrated for accuracy using a proprietary patent-pending process. It includes heavy-duty stainless steel pressure transducers designed for use with CO2/R744 systems at transcritical pressures and features a multicolored LED readout indicating pressure range and an analog output for precise pressure monitoring. This device’s case is both dust and weather resistant and comes equipped with 6-foot pressure-transducer cables and a 6-foot power cable, allowing for significant versatility in its placement.

02

Contact Westermeyer Industries for more information. 

02 Dosier técnico

Especificaciones

17 datos · según lo publicado por Westermeyer

Refrigerante
CO₂
Categoría
Controladores y variadores de frecuencia

01Límites de funcionamiento

2 entradas

Metrics controlled (temperature, pressure)
Maximum Working Pressure: 2,175 psig
Operating temperature range
Electronics Enclosure Ambient: -40 °F to 175 °F; Transducer Ambient: -22 °F to 185 °F; Transducer Refrigerant: -40 °F to 275 °F

02Refrigerante

2 entradas

Sensor: ppm range of gas detected
N/A
Refrigerant
CO₂

03Componentes y opciones

1 entrada

Valves controlled
N/A

04Control y sistema eléctrico

8 entradas

Controller, inverter & sensors
Refri-Shield™ RDP-01 Differential Pressure Monitor
Remote monitoring?
Yes
Proprietary or open architecture?
Proprietary
Variable-speed control?
N/A
Automatic fault detection?
Yes
Communication type
Voltage Output; 0.5—4.5 V at 0—20 PSID; Minimum Accepted Load: 500 ohms. +/- 2 PSID accuracy.
Power consumption
<50mA
Type of sensor
Transducer

05Construcción y dimensiones

1 entrada

Equipment focus (racks, cases, etc)
Rack – Pressure Differential Monitor

06Certificación y mercados

3 entradas

Region
Africa, Asia, Australia & NZ, China, Europe, Global, Japan, North America, South America
Application
Pressure Differential Monitor for Coalescing Oil Separators in Transcritical CO₂ Applications
Certification? UL/CE
UL
Westermeyer Industries logo

Hable con Westermeyer sobre RDP-01T Differential Pressure Monitor.

Envíe su consulta a Westermeyer: solicite especificaciones, precios y disponibilidad para su proyecto.

Compartir