Zum Inhalt springen
Beta

Das ist die neue NaturalRefrigerants.com. Ein technisches oder inhaltliches Problem entdeckt? Schreiben Sie uns an info@naturalrefrigerants.com.

Westermeyer

RDP-01T Differential Pressure Monitor

The RDP-01T Differential Pressure Monitor is part of the Refri-Shield™️ line of system monitoring products.

Diese Produktseite ist noch nicht auf Deutsch verfügbar – hier das englische Original.

RDP-01T Differential Pressure Monitor

Abb. 01 – RDP-01T Differential Pressure Monitor

01 Überblick

It is designed to indicate when the filter element of a coalescing oil separator needs to be serviced and replaced by measuring the pressure differential across the inlet and outlet. This model features transducers designed for use with CO₂ systems at transcritical pressures.

01

Westermeyer RDP-01T Differential Pressure Monitor When the filter element of a coalescing oil separator is contaminated, performance and efficiency are negatively affected. A differential pressure monitor is used to monitor, both visually and electronically, when the filter is contaminated and needs to be replaced. 

The Refri-Shield™️ RDP-01T Differential Pressure Monitor is factory-calibrated for accuracy using a proprietary patent-pending process. It includes heavy-duty stainless steel pressure transducers designed for use with CO2/R744 systems at transcritical pressures and features a multicolored LED readout indicating pressure range and an analog output for precise pressure monitoring. This device’s case is both dust and weather resistant and comes equipped with 6-foot pressure-transducer cables and a 6-foot power cable, allowing for significant versatility in its placement.

02

Contact Westermeyer Industries for more information. 

02 Technisches Dossier

Technische Daten

17 Datenpunkte · wie von Westermeyer veröffentlicht

Kältemittel
CO₂
Kategorie
Komponenten

01Einsatzgrenzen

2 Einträge

Metrics controlled (temperature, pressure)
Maximum Working Pressure: 2,175 psig
Operating temperature range
Electronics Enclosure Ambient: -40 °F to 175 °F; Transducer Ambient: -22 °F to 185 °F; Transducer Refrigerant: -40 °F to 275 °F

02Kältemittel

2 Einträge

Sensor: ppm range of gas detected
N/A
Refrigerant
CO₂

03Komponenten & Optionen

1 Eintrag

Valves controlled
N/A

04Regelung & Elektrik

8 Einträge

Controller, inverter & sensors
Refri-Shield™ RDP-01 Differential Pressure Monitor
Remote monitoring?
Yes
Proprietary or open architecture?
Proprietary
Variable-speed control?
N/A
Automatic fault detection?
Yes
Communication type
Voltage Output; 0.5—4.5 V at 0—20 PSID; Minimum Accepted Load: 500 ohms. +/- 2 PSID accuracy.
Power consumption
<50mA
Type of sensor
Transducer

05Ausführung & Abmessungen

1 Eintrag

Equipment focus (racks, cases, etc)
Rack – Pressure Differential Monitor

06Zertifizierung & Märkte

3 Einträge

Region
Africa, Asia, Australia & NZ, China, Europe, Global, Japan, North America, South America
Application
Pressure Differential Monitor for Coalescing Oil Separators in Transcritical CO₂ Applications
Certification? UL/CE
UL
Westermeyer Industries logo

Sprechen Sie mit Westermeyer über RDP-01T Differential Pressure Monitor.

Senden Sie Ihre Anfrage an Westermeyer – fragen Sie nach technischen Daten, Preisen und Verfügbarkeit für Ihr Projekt.

Teilen